Connections

1. USB serial port
2. NTP data line suppressor
3. UPS output sockets
4. Input socket and fuse
5. Fan / air vents
Control panel
 |
1. Alarm
2. Operation with battery
3. Normal operation
4. On / Off
5. Load present
6. Load level (5 steps)
7. General Alarm
8. Battery fault / Replace the battery
9. Overload
10. Battery capacity
11. Normal mode / Battery mode (flashing)
12. Automatic Voltage / Regulation active
|
Technical data
Sn |
600 VA |
650 VA |
800 VA |
1000 VA |
1500 VA |
2000 VA |
Pn |
360 W |
360 W |
480 W |
600 W |
900 W |
1200 W |
Input / output |
1/1 |
Input |
Rated voltage |
230 V |
Voltage tolerance |
170 V - 280 V |
Rated frequency |
50 / 60 Hz with automatic selection |
Mains connection |
IEC320 socket |
Output |
Automatic Voltage Regulation (AVR) |
• |
• |
• |
• |
• |
• |
Rated voltage |
230 V ±10% |
Rated frequency |
50/60 Hz ±1% |
Wave form |
Step wave |
Protection |
Overload, significant discharge and short circuit |
Connections |
4 x IEC 320 (C13) (1) |
6 x IEC 320 (C13) (1) |
Batteries |
Type |
Sealed lead-acid maintenance free - expected life 3/5 years |
Back-up time (2) |
15 min |
15 min |
20 min |
45 min |
55 min |
60 min |
Communication |
Interface |
- |
USB |
Local communication software |
- |
Local View |
Telephone protection |
- |
NTP data line suppressor |
UPS cabinet |
Dimensions W x D x H |
100 x 290 x 145 mm |
145 x 345 x 165 mm |
145 x 390 x 205 mm |
Weight |
5.0 kg |
5.2 kg |
6.0 kg |
9.7 kg |
11.2 kg |
12 kg |
Standards |
Safety |
IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2 |
EMC |
IEC/EN 62040-2, AS 62040.2 |
Product declaration |
CE, RCM (E2376) |
|
(1) Australian standard sockets on Netys PE models specific for Australia.
(2) PC + 17” LCD monitor.
Tidak ada gambar tambahan untuk produk ini.